Cam action and characteristics are selectable
Value action can be switched between direct and reverse by shifting 90[deg] the position of the feedback lever A from A to B.(However the output piping has to be changed.) Also, the structure is such that the characteristics can be changed by selecting the cam. For linear motion, the standard cam can be used to select the characteristics of linear and equal %. Select any of these rotary motion, change the cam to obtain proper equal % characteristics, square-law characteristics, and equal reverse % (optional).
Specs | Single acting | double acting |
Input signal (pressure) | standard: 20 to 100 kPa
(1/2 split range is available with easy adjustment) |
|
supply air pressure | 0.14~0.7MPa/140~700kPa | |
stroke / angle | Linear motion : 10~100mm
Rotary motion : 60°~90° |
|
Air connection (pressure gauge connection) | Standard: Rc 1/4(pressure gauge Rc 1/8)
Option: NPT 1/4(pressure gauge NPT 1/8) |
|
*1 pressure gauge (output pressure) |
Stadard: 0~0.2MPa、0~0.4MPa、0~1.0MPa (R) Option: kPa、psi、bar (R, NPT) |
|
Construcion | Non-explosion proof | |
Cam | Standard: Linear characteristics
Option: non-linear characteristics |
|
Ambient Temp. | Standard: (S) -20~83℃
Low temp. construction: (L) -50~60℃ High temp. construction: (H) 0~100℃ |
|
Weight | approx. 1.3kg | approx. 1.4kg |
Materials | Body: Aluminum diecastings (Special Anodize)
Cover: PBT resin(Mixed glass fiber)、Option: Aluminum diecastings (Special Anodize) |
*1 please contact us for psi and bar display
characteristics | Single acting | Double acting |
Linearity | ±1.0%F.S | ±2.0%F.S |
hysteresis | 1.0%F.S | 1.0%F.S |
repeatability | 0.3%F.S | 0.5%F.S |
sensitivity | 0.2%F.S | 0.5%F.S |
change of supply pressure | 0.2%/0.01MPa | 0.3%/0.01MPa |
orientation effect (10deg / 90deg) | 0.2% / 4.0% | |
endurance to vibration | 1%/1G | |
air consumption(Nl/min) (Nl/min) |
5.0/0.14MPa at 50% output pressure |
10/0.4MPa at 75% output pressure |
Max Cv (Nl/min) (Nl/min) |
160/0.14MPa | 370/0.4MPa |
on condition that Output is open to air (orifce dia 5mm) |
Pilot Relay | Max Cv. (Nl/min) |
Air Consumption (Nl/min) |
||||
single acting (0.14MPa) |
double acting (0.4MPa) |
|||||
XE | XP | XE | XP | |||
Standard | 160 | 370 | 5.0 | 5.0 | 10 | 10 |
Stable | 160 | 370 | 7.0 | 8.0 | 14 | 16 |
Fast | 180 | 450 | 7.0 | 8.0 | 14 | 16 |
Specifications above is effected by actuator spec.