P/P Positioner XP100

Cam action and characteristics are selectable

Value action can be switched between direct and reverse by shifting 90[deg] the position of the feedback lever A from A to B.(However the output piping has to be changed.) Also, the structure is such that the characteristics can be changed by selecting the cam. For linear motion, the standard cam can be used to select the characteristics of linear and equal %. Select any of these rotary motion, change the cam to obtain proper equal % characteristics, square-law characteristics, and equal reverse % (optional).

Specs Single acting double acting
Input signal (pressure) standard: 20 to 100 kPa

(1/2 split range is available with easy adjustment)

supply air pressure 0.14~0.7MPa/140~700kPa
stroke / angle Linear motion : 10~100mm

Rotary motion : 60°~90°

Air connection (pressure gauge connection) Standard: Rc 1/4(pressure gauge Rc 1/8)

Option: NPT 1/4(pressure gauge NPT 1/8)

*1
pressure gauge
(output pressure)
Stadard: 0~0.2MPa、0~0.4MPa、0~1.0MPa (R)
Option: kPa、psi、bar (R, NPT)
Construcion Non-explosion proof
Cam Standard: Linear characteristics

Option: non-linear characteristics

Ambient Temp. Standard: (S) -20~83℃

Low temp. construction: (L) -50~60℃

High temp. construction: (H) 0~100℃

Weight approx. 1.3kg approx. 1.4kg
Materials Body: Aluminum diecastings (Special Anodize)

Cover: PBT resin(Mixed glass fiber)、Option: Aluminum diecastings (Special Anodize)

scrollable

*1 please contact us for psi and bar display

characteristics Single acting Double acting
Linearity ±1.0%F.S ±2.0%F.S
hysteresis 1.0%F.S 1.0%F.S
repeatability 0.3%F.S 0.5%F.S
sensitivity 0.2%F.S 0.5%F.S
change of supply pressure 0.2%/0.01MPa 0.3%/0.01MPa
orientation effect (10deg / 90deg) 0.2% / 4.0%
endurance to vibration 1%/1G
air consumption(Nl/min)
(Nl/min)
5.0/0.14MPa
at 50% output pressure
10/0.4MPa
at 75% output pressure
Max Cv (Nl/min)
(Nl/min)
160/0.14MPa 370/0.4MPa
on condition that Output is open to air (orifce dia 5mm)
Pilot Relay Max Cv.
(Nl/min)
Air Consumption
(Nl/min)
single acting
(0.14MPa)
double acting
(0.4MPa)
XE XP XE XP
Standard 160 370 5.0 5.0 10 10
Stable 160 370 7.0 8.0 14 16
Fast 180 450 7.0 8.0 14 16

Specifications above is effected by actuator spec.

Request information about this product